How the three-phase power calculator works
A balanced three-phase system delivers power on three conductors whose voltages are 120° apart. Total power uses the line-to-line voltage and √3, which comes from the geometry of the three phases.
P (kW) = S × power factor
Current I = P × 1,000 ÷ (√3 × V × PF)
Common US three-phase voltages are 208 V, 240 V and 480 V. The horsepower figure is electrical input divided by 746 W/hp; a motor's shaft output is lower because of its efficiency, typically 90% to 96% for modern premium-efficiency motors.
Worked example
A 480 V motor drawing 50 A at 0.85 power factor uses √3 × 480 × 50 = 41.57 kVA of apparent power and 41.57 × 0.85 = 35.33 kW of real power, about 47.4 hp of electrical input. Reactive power is 21.9 kVAR.
Frequently asked questions
Why is √3 used in three-phase power?
Because line-to-line voltage is √3 times the phase voltage in a wye system, and phase currents are 120° apart.
How do I convert kW to amps in three-phase?
Amps = kW × 1,000 ÷ (√3 × volts × PF).
What is the difference between kW and kVA?
kW is real power; kVA is apparent power. kW = kVA × power factor.
Is 208 V three-phase the same as 240 V?
No. 208 V comes from a 120/208 V wye system; 240 V usually from a delta system.